LOW VOLTAGE · PRIMARY DISTRIBUTION

LPCPOWER CENTER

Your plant’s power.
Engineered around you.

Low-voltage switchboards for centralised power distribution. Modular construction, metal-enclosed sections and configurations developed for industrial plants and large commercial facilities.

ICEL / LPCRANGE RATINGS

RATED CURRENT UP TO

6,300AInA

OPERATIONAL VOLTAGE UP TO

690V ACUe

SHORT-TIME WITHSTAND UP TO

100kA / 1 sIcw

Ratings depend on configuration. Voltage ratings depend on the installed equipment.

IEC 61439-1 / IEC 61439-2FORMS 3a · 3b · 4bTECHNICAL CATALOGUE / V2.0 · 04.03.2024

01 / TECHNICAL SPECIFICATIONS

THE RATINGS YOU NEED.
RIGHT AT YOUR FINGERTIPS.

Explore electrical ratings, protection, service conditions and materials.

Electrical ratings
CharacteristicSymbolCatalogue value
Rated operational voltageUeUp to 690 V AC / 750 V DC
Rated insulation voltageUiUp to 1,000 V AC / 1,500 V DC
Rated impulse withstand voltageUimpUp to 12 kV
Rated frequencyfn50–60 Hz
Rated assembly currentInAUp to 6,300 A
Rated short-time withstand currentIcwUp to 100 kA / 1 s
Rated peak withstand currentIpkUp to 220 kA
Overvoltage category—Up to IV
Pollution degree—3

Ue, Ui and Uimp depend on the installed equipment. Range maxima apply to the configuration specified for the project.

Protection
CharacteristicSymbolCatalogue value
Reference standards—IEC 61439-1 / IEC 61439-2
Forms of internal separation—3a · 3b · 4b
With doors closedIPIP30
Horizontal roof surfaceIPIP3XD
With doors openIPIP2X
Mechanical impact on the metal enclosureIKIK10 — IEC/EN 62262
Resistance to corrosion—Severity A

IP ratings according to IEC/EN 60529. Other degrees of protection on request.

Service conditions
CharacteristicSymbolCatalogue value
Installation—Stationary, indoor, in environment A
Minimum ambient temperature—−5 °C
Maximum ambient temperature—+40 °C
Average temperature over 24 hours—35 °C
Maximum relative humidity—50% at 40 °C
Altitude—Up to 2,000 m above sea level

The catalogue describes environment A as a network supplied by a dedicated MV/LV transformer.

Materials
CharacteristicSymbolCatalogue value
Frame and internal partitions—Pre-galvanised sheet steel
Doors and side panels—Semigloss powder coating
Standard colourRAL7035 — light grey
Main and distribution busbars—Bare flat electrolytic copper
Auxiliary wiring—Black N07-VK; other cables on request
Insulating material groupCTIII — 400 ≤ CTI < 600 V
Flammability classification—UL 94 V-0
Insulating material composition—Halogen- and silicone-free
Insulators—Glass-fibre-reinforced polyester — 130 °C
Selected internal insulating parts—Polycarbonate — ≥120 °C

Other colours on request.

02 / CONSTRUCTION

EVERY FUNCTION.
ITS OWN SPACE.

Independent sections, bolted together to suit the project. Main busbars and auxiliary wiring connect the assembly.

01

Front section

Circuit-breakers, metering and auxiliaries.

Circuit-breaker compartments enclosed by metal partitions and individual hinged front doors, with ventilation, auxiliary wiring passages and circuit-breaker fixing accessories.

02

First rear zone

Busbars and branch connections.

Horizontal main busbars and vertical distribution busbars on the inner right-hand side. Lower-rated circuits branch from the distribution busbars; higher-rated circuits connect directly to the main or branch busbars.

03

Second rear zone

Power connections.

Space for cable or busbar connections. The rear of each section is closed by full-height doors.

MAIN BUSBARS1,250–6,300 A

3P / 4P + PE · N/2, N, PEN

DISTRIBUTION BUSBARS630–3,200 A

Mounted vertically on the inner right-hand side.

Frame and insulation

Riveted frame with metal panels and partitions. The entire metal structure is earthed. Air-insulated busbars and self-extinguishing insulating supports with mechanical strength and anti-tracking properties.

Natural ventilation

Front and rear louvers, ducts alongside the compartments and roof outlets provide natural cooling. In the IAC version, ventilation flaps close automatically in the event of an internal arc.

Auxiliaries and load diversity

Limited auxiliary equipment and terminals can share an upper compartment; larger quantities use dedicated compartments. The combination of functional units accounts for load diversity and section current-carrying capacity.

Coordinated construction with medium-voltage switchboards allows compact transformer substations, with the arrangement defined for the project.

FOR THE DESIGNERHow air flows through the switchboard

LPC / SHEET 03

Natural ventilation of the section

LPC: natural ventilation layout of the section.ROOF OUTLETSHot air leaves throughthe upper exhaust ducts.DUCTS ALONGSIDE THE COMPARTMENTSCooling paths forthe circuit-breakers.BUSBAR AND CONNECTION ZONEAir rises through therear part of the section.AIR INLETSLouvers on compartment doors andlower front and rear panels.SOURCE AIRFLOW PATHS · NOT TO SCALE
Range
LPC
Reference
V2.0 / p. 7
Dimensions
—
Layout
LPC
Illustrative drawing · not to scale. Confirm against project drawings.Catalogue V2.0 / p. 7

03 / FORMS OF INTERNAL SEPARATION

THREE FORMS.
CLEAR DIFFERENCES.

Compare the separation of busbars, functional units and terminals.

Conceptual separation diagram. It does not represent the switchboard’s physical layout.

3a

Busbars and terminals in a shared zone.

Busbars are separated from all functional units, and functional units are separated from one another. Terminals for external conductors are not separated from the busbars.

Terminals belonging to different functional units are not separated from one another. Terminals and external conductors are separated from the functional units.

Conceptual separation diagram. It does not represent the switchboard’s physical layout.

3b

Terminals separated from the busbars.

Busbars remain separated from all functional units, and functional units from one another. Terminals and external conductors are separated from the busbars.

Terminals belonging to different functional units are not separated from one another. Terminals and external conductors are separated from the functional units.

Conceptual separation diagram. It does not represent the switchboard’s physical layout.

4b

Each unit has separately enclosed terminals.

Busbars and functional units are separated. The terminals associated with each functional unit are also separated from the busbars and from the terminals of every other unit.

Terminals are in a compartment separate from the associated functional unit. Functional units are also separated from one another.

BusbarsFunctional unitsTerminals

The catalogue’s explanatory page also compares form 4a, with terminals in the same compartment as their functional unit. The stated LPC versions are 3a, 3b and 4b; in 4b terminals occupy a separate space from their associated functional unit.

FOR THE DESIGNERSeparation inside the switchboard

Side sections and plans of the three versions. The drawings preserve the source construction details for moulded-case and air circuit-breakers.

LPC / SHEET 04

Construction separation · MCCB

LPC side and plan separation views, Moulded-case circuit-breakers3a3b4bSIDE VIEW · FRONT ON THE RIGHTPLAN VIEWGEOMETRY AND PARTITIONS RETAINED FROM THE ORIGINAL DRAWING
Circuit-breakers
MCCB
Forms
3a / 3b / 4b
Configurations
3
Reference
V2.0 / p. 9
Illustrative drawing · not to scale. Confirm against project drawings.Catalogue V2.0 / p. 9

LPC / SHEET 05

Construction separation · ACB

LPC side and plan separation views, Air circuit-breakers3a3b4bSIDE VIEW · FRONT ON THE RIGHTPLAN VIEWGEOMETRY AND PARTITIONS RETAINED FROM THE ORIGINAL DRAWING
Circuit-breakers
ACB
Forms
3a / 3b / 4b
Configurations
3
Reference
V2.0 / p. 9
Illustrative drawing · not to scale. Confirm against project drawings.Catalogue V2.0 / p. 9

04 / CIRCUIT-BREAKERS AND ACCESS

THE RIGHT CONFIGURATION.
FOR EACH CIRCUIT.

Air circuit-breakers (ACBs) and moulded-case circuit-breakers (MCCBs), in fixed, plug-in and withdrawable versions.

FixedFixed circuit-breaker installation.

Plug-inIn service: main and auxiliary circuits connected. Removed: device outside the compartment, with both circuits disconnected from the stationary part.

WithdrawableFour positions, illustrated below. Guides, auxiliary levers and locking catches allow movement and locking in the specified positions.

WITHDRAWABLE CIRCUIT-BREAKER

Service

Circuit-breaker inside the compartment; main and auxiliary circuits connected to the fixed part.

Main circuits
Connected
Auxiliary circuits
Connected
Physical position
Inside the compartment

WITHDRAWABLE CIRCUIT-BREAKER

Test

Circuit-breaker inside the compartment; main circuits disconnected and auxiliary circuits connected to the fixed part.

Main circuits
Disconnected
Auxiliary circuits
Connected
Physical position
Inside the compartment

WITHDRAWABLE CIRCUIT-BREAKER

Disconnected

Circuit-breaker inside the compartment; main and auxiliary circuits disconnected from the fixed part.

Main circuits
Disconnected
Auxiliary circuits
Disconnected
Physical position
Inside the compartment

WITHDRAWABLE CIRCUIT-BREAKER

Removed

Circuit-breaker removed from the compartment.

Main circuits
Disconnected
Auxiliary circuits
Disconnected
Physical position
Outside the compartment

This view describes circuit connection states. Access, interventions and service continuity depend on the switchboard configuration and the applicable procedures.

FOR THE DESIGNERStandard compartments and cable connections

Explore the combinations listed on page 12 of the catalogue. Dimensions refer to compartments, not the overall section width.

28 rows

Scroll horizontally to view all columns →

Circuit-breaker compartments and cable connections — LPC catalogue, p. 12
TypeSize (A)PolesVersionVertical compartment (mm)Horizontal compartment (mm)Connections per phaseScrew
ACB1250 - 16003PF-W500 x H 527—4M12
ACB1250 - 16004PF-W500 x H 527—4M12
ACB2000 - 25003PF-W600 x H 527—6M12
ACB2000 - 25004PF-W600 x H 527—6M12
ACB3200 - 40003PF-W700 x H 651—12M12
ACB3200 - 40004PF-W700 x H 651—12M12
ACB5000 - 63003PF-W1000 x H 651—12M12
ACB5000 - 63004PF-W1100 x H 651—12M12
MCCB100 - 1603P-4PF - D425 x H 527600 x H 1552M8
MCCB2503P-4PF - D425 x H 527600 x H 1862M8
MCCB2503PW425 x H 527600 x H 1862M8
MCCB2504PW425 x H 527600 x H 2172M8
MCCB4003PF - D425 x H 527600 x H 2172M12
MCCB4004PF - D425 x H 527600 x H 2482M12
MCCB4003PW425 x H 527600 x H 2172M12
MCCB4004PW425 x H 527600 x H 2792M12
MCCB630 - 8003PF- D425 x H 527600 x H 2792M12
MCCB630 - 8004PF- D425 x H 527600 x H 3412M12
MCCB630 - 8003PW425 x H 527700 x H 3102M12
MCCB630 - 8004PW425 x H 527700 x H 3722M12
MCCB1000 - 12503PF425 x H 527700 x H 3104M12
MCCB1000 - 12504PF425 x H 527700 x H 3724M12
MCCB1000 - 12503PW425 x H 527700 x H 3724M12
MCCB1000 - 12504PW425 x H 527700 x H 4344M12
MCCB16003PF425 x H 651
500 x H 527
—4M12
MCCB16004PF425 x H 651
500 x H 527
—4M12
MCCB16003PW425 x H 651
500 x H 527
—4M12
MCCB16004PW500 x H 527—4M12
FOR THE DESIGNERTen sections. Fronts and single-line diagrams.

Ten section examples, each with its own front view and single-line diagram. Select a code to compare device and branch arrangements.

Eight stacked moulded-case circuit-breakers with branches from the vertical busbar.

LPC / SHEET M0S

M0S · front and single-line diagram

LPC M0S: catalogue front view and single-line diagram.FRONT VIEWSINGLE-LINE DIAGRAMM0SLHCATALOGUE EXAMPLE · NOT TO SCALE
Drawing code
M0S
Devices in example
8
Height label
H
Source
V2.0 / p. 10
Illustrative drawing · not to scale. Confirm against project drawings.Catalogue V2.0 / p. 10

Five moulded-case circuit-breakers and one larger device in the lower section.

LPC / SHEET MVS

MVS · front and single-line diagram

LPC MVS: catalogue front view and single-line diagram.FRONT VIEWSINGLE-LINE DIAGRAMMVSLHCATALOGUE EXAMPLE · NOT TO SCALE
Drawing code
MVS
Devices in example
6
Height label
H
Source
V2.0 / p. 10
Illustrative drawing · not to scale. Confirm against project drawings.Catalogue V2.0 / p. 10

One air circuit-breaker; the diagram shows a branch from the upper busbar.

LPC / SHEET M01

M01 · front and single-line diagram

LPC M01: catalogue front view and single-line diagram.FRONT VIEWSINGLE-LINE DIAGRAMM01LHCATALOGUE EXAMPLE · NOT TO SCALE
Drawing code
M01
Devices in example
1
Height label
H
Source
V2.0 / p. 10
Illustrative drawing · not to scale. Confirm against project drawings.Catalogue V2.0 / p. 10

Two air circuit-breakers; the central busbar has one upper and one lower branch.

LPC / SHEET M02

M02 · front and single-line diagram

LPC M02: catalogue front view and single-line diagram.FRONT VIEWSINGLE-LINE DIAGRAMM02LHCATALOGUE EXAMPLE · NOT TO SCALE
Drawing code
M02
Devices in example
2
Height label
H
Source
V2.0 / p. 10
Illustrative drawing · not to scale. Confirm against project drawings.Catalogue V2.0 / p. 10

Two vertically stacked moulded-case circuit-breakers, with branches above and below the central busbar.

LPC / SHEET M2V

M2V · front and single-line diagram

LPC M2V: catalogue front view and single-line diagram.FRONT VIEWSINGLE-LINE DIAGRAMM2VHCATALOGUE EXAMPLE · NOT TO SCALE
Drawing code
M2V
Devices in example
2
Height label
H
Source
V2.0 / p. 11
Illustrative drawing · not to scale. Confirm against project drawings.Catalogue V2.0 / p. 11

Four moulded-case circuit-breakers in two columns; two upper and two lower branches.

LPC / SHEET M4V

M4V · front and single-line diagram

LPC M4V: catalogue front view and single-line diagram.FRONT VIEWSINGLE-LINE DIAGRAMM4VHCATALOGUE EXAMPLE · NOT TO SCALE
Drawing code
M4V
Devices in example
4
Height label
H
Source
V2.0 / p. 11
Illustrative drawing · not to scale. Confirm against project drawings.Catalogue V2.0 / p. 11

Front without circuit-breakers; the diagram shows the conductor route only.

LPC / SHEET M0B

M0B · front and single-line diagram

LPC M0B: catalogue front view and single-line diagram.FRONT VIEWSINGLE-LINE DIAGRAMM0BHCATALOGUE EXAMPLE · NOT TO SCALE
Drawing code
M0B
Devices in example
0
Height label
H
Source
V2.0 / p. 11
Illustrative drawing · not to scale. Confirm against project drawings.Catalogue V2.0 / p. 11

Three vertically stacked air circuit-breakers and three busbar levels shown in the diagram.

LPC / SHEET M03

M03 · front and single-line diagram

LPC M03: catalogue front view and single-line diagram.FRONT VIEWSINGLE-LINE DIAGRAMM03LHCATALOGUE EXAMPLE · NOT TO SCALE
Drawing code
M03
Devices in example
3
Height label
H
Source
V2.0 / p. 11
Illustrative drawing · not to scale. Confirm against project drawings.Catalogue V2.0 / p. 11

Two moulded-case circuit-breakers in the upper section and one air circuit-breaker in the lower section.

LPC / SHEET M3B

M3B · front and single-line diagram

LPC M3B: catalogue front view and single-line diagram.FRONT VIEWSINGLE-LINE DIAGRAMM3BLHCATALOGUE EXAMPLE · NOT TO SCALE
Drawing code
M3B
Devices in example
3
Height label
H
Source
V2.0 / p. 11
Illustrative drawing · not to scale. Confirm against project drawings.Catalogue V2.0 / p. 11

One air circuit-breaker in the upper section and two moulded-case circuit-breakers in the lower section.

LPC / SHEET M3A

M3A · front and single-line diagram

LPC M3A: catalogue front view and single-line diagram.FRONT VIEWSINGLE-LINE DIAGRAMM3ALHCATALOGUE EXAMPLE · NOT TO SCALE
Drawing code
M3A
Devices in example
3
Height label
H
Source
V2.0 / p. 11
Illustrative drawing · not to scale. Confirm against project drawings.Catalogue V2.0 / p. 11
FOR THE DESIGNERFrom individual sections to a complete assembly

A complete catalogue example, with fronts and connections shown in one drawing. The two BLINDO 2500A labels apply to this arrangement.

LPC / SHEET E1

A complete assembly example

LPC example: M0B, M03 P12–P14, MS2 P15–P16; two BLINDO 2500A connections; MIS, RIF and kWh annotations.ASSEMBLY EXAMPLE · ORIGINAL DRAWINGLABELS AND CONNECTIONS RETAINED FROM THE EXAMPLE ON PAGE 13
Columns in example
6
Section labels
M0B · M03 · MS2
Circuit tags
P12–P16
Connections shown
2 × BLINDO 2500A
Illustrative drawing · not to scale. Confirm against project drawings.Catalogue V2.0 / p. 13
Reading the example — left to right
SectionDrawing codeCircuit reference
01M0B—
02M03P12
03M03P13
04M03P14
05MS2P15
06MS2P16

05 / TESTING AND REFERENCES

PERFORMANCE.
PUT TO THE TEST.

The reports and certificates listed in the LPC catalogue, with separate values and references for each test.

01

ACAE – LOVAG /IT 13.121

Dielectric properties and temperature rise

EN 61439-2

  • 2,200 V for 5 s; 8 and 12 kV impulse
  • Temperature-rise test at 6,300 A
02

ACAE – LOVAG /IT 14.023

Short-circuit withstand

EN 61439-2

  • Main circuits: 100 kA for 1.1 s / 220 kA peak
  • Protective circuits: 60 kA for 1.1 s / 136 kA peak
  • Protective circuit verification: <0.1 Ω
03

INTEK /RP2012-0404-00

Enclosure and protection

EN 60529 · EN 62262 · EN 61439-1

  • Degrees of protection IP30 and IP31
  • IK10 mechanical impact
  • Corrosion resistance, type A
04

ACAE – LOVAG /IT 24.011

Internal arcing test

IEC TR 61641 Ed. 3

  • 100 kA for 0.3 s — criteria 1 to 5
  • Dielectric test
05

EUCENTRE (ACCREDIA) /ICE039E23_TR_1

Seismic test

IEC & IEEE

  • Severity level II
  • 1.0 g horizontal / 0.8 g vertical

References listed in catalogue V2.0 dated 4 March 2024. Test results apply to the tested configurations; applicability to the supplied assembly is checked during project engineering.

06 / DIMENSIONS AND INSTALLATION

THE SWITCHBOARD.
IN ITS SPACE.

Range dimensions are the starting point. The final arrangement of sections and overall dimensions are defined in the project drawings.

2,250 mmWIDTH

Illustrative diagram, not to scale. No project-specific configuration is represented.

Nominal body height
2,250 mm
Base depth
1,000 / 1,200 / 1,400 mm
Widths in the general data sheet
500 / 600 / 700 / 850 / 1,000 / 1,100 mm

Dimensions listed in the general technical data sheet (p. 4). They depend on section type; not all combinations are equivalent or interchangeable.

01

Level floor

Install on a level floor. Foundation channels are available on request.

02

M12 fixing

The catalogue normally specifies M12 expansion anchors in the provided fixing holes.

03

Front and rear access

The installation diagram shows over 1,200 mm at the front and over 1,000 mm at the rear. Confirm clearances against the project drawings.

The installation drawing shows an 80 mm protrusion above the switchboard body. This is not a ceiling-clearance dimension: check the overall height against the project drawings.

FOR THE DESIGNERSection dimensions and installation details

These tables retain the dimensional groups shown on pages 10 and 14. The values are catalogue references: they do not authorise arbitrary combinations and do not replace project drawings.

Moulded-case circuit-breaker sections — dimensions listed on p. 10
Section typeWidth L (mm)Depth P (mm)Height H (mm)
M0S / MVS600 / 7001000 / 1200 / 14002250
MV25001200 / 14002250
MV4850 / 10001200 / 14002250
M0B3001000 / 1200 / 14002250
Air circuit-breaker sections — dimensions listed on p. 10
Section typeWidth L (mm)Depth P (mm)Height H (mm)
M01 / MV2600 / 700 / 850 / 1000 / 12001200 / 14002250
MV3600 / 700 / 8501200 / 14002250
M3A\B850 / 1000 / 11001200 / 14002250

LPC / SHEET 01

Overall dimensions and access

LPC installation: body height, roof protrusion and access clearances.REARFRONT2 25080>1 000P>1 200
Body height
2 250 mm
Roof protrusion
80 mm
Rear access
>1 000 mm
Front access
>1 200 mm
Dimensions in mm · not to scale. Confirm against project drawings.Catalogue V2.0 / p. 14

LPC / SHEET 02

Base openings and fixings

LPC base openings and fixings: M0S and section layouts.M0SL1 000 / 1 200 / 1 400701007020090LSECTIONSL1 000 / 1 200 / 1 40070100100L110090L2LABELS L / L1 / L2 ARE RETAINED FROM THE SOURCE
Depth P
1 000 / 1 200 / 1 400 mm
M0S opening
200 × L mm
Section opening
L1 × L2
Reference
L / L1 / L2
Dimensions in mm · not to scale. Confirm against project drawings.Catalogue V2.0 / p. 14
Base fixing and openings — M0S table, p. 14
TypeP (mm)L (mm)L1 (mm)
M0S1000600300
M0S1200600500
M0S1400600500
M0S1000700300
M0S1200700500
M0S1400700500
Base fixing and openings — section table, p. 14
TypeL (mm)L1 (mm)L2 (mm)
M01/M02/MV2500300600
M01/M02/MVS600400600
M01/M02/MVS700500600
M01/M02/M3A–B/MV4850650600
M01/M02/M3A–B1000800600
M01/M02/M3A–B12001000600

QUALITY AND PRODUCT LIFE CYCLE

FROM MANUFACTURE.
TO END OF LIFE.

The catalogue refers to ISO 9001 and ISO 14001 management systems, provides for a quality certificate on supply, and states that service life can reach 30 years, provided the prescribed maintenance instructions are followed.

Metals, insulating materials and packaging are managed according to the materials actually present and local requirements. ICEL provides guidance for subsequent recycling or disposal.

CATALOGUE REFERENCEMaterial by material. Through end of life.

Materials and recycling or disposal methods at end of life.

Materials and end of life — catalogue, p. 15
MaterialRoute stated in the catalogue
Metals: Fe, Cu, Al, Ag, Zn, W and othersSeparate collection and recycling
ThermoplasticsRecycling or disposal
Epoxy resinSeparation of metal and disposal of the remainder
RubberDisposal
Transformer dielectric oilRemoval from equipment, followed by recycling or disposal
SF6 gasRecovery from equipment, followed by recycling or disposal
Wood packagingRecycling or disposal
Foil packagingRecycling or disposal

07 / TECHNICAL FAQ

THE RIGHT QUESTIONS.
CLEAR ANSWERS.

The key information for a technical discussion about your plant.

Have a specific requirement?
What applications is LPC Power Center designed for?

LPC is a primary low-voltage distribution switchboard for transformer and distribution substations in industrial plants and large commercial facilities. Its modular construction allows sections to be combined to suit the project’s electrical diagram.

Explore the details
Is LPC Power Center suitable for LV distribution up to 6,300 A?

The catalogue lists operational voltages up to 690 V AC or 750 V DC and a rated assembly current up to 6,300 A. Rated short-time withstand current Icw is up to 100 kA for 1 s, with Ipk up to 220 kA. Voltage ratings depend on the installed equipment; the final configuration is defined for the project.

Explore the details
Which circuit-breaker types and brands can be integrated into the Power Center?

LPC accommodates air circuit-breakers (ACBs) and moulded-case circuit-breakers (MCCBs), in fixed, plug-in or withdrawable versions. ICEL integrates ABB, Siemens and Schneider low-voltage equipment selected to suit the specification. Dimensions, connections and ratings of the specific combination are checked during engineering. For withdrawable devices, the catalogue distinguishes service, test, disconnected and removed positions.

Explore the details
How do forms 3a, 3b and 4b differ?

All three forms separate busbars from functional units and functional units from one another. In form 3a, terminals are not separated from the busbars; in form 3b, they are. In form 4b, each unit’s terminals are also separated from other units’ terminals and located in a compartment separate from the associated functional unit.

Explore the details
Which type tests and verifications are documented for LPC?

The LPC catalogue documents dielectric and temperature-rise verification, short-circuit withstand, enclosure and protection tests, plus internal arcing and seismic tests. References include ACAE–LOVAG IT 13.121 and IT 14.023, INTEK RP2012-0404-00, ACAE–LOVAG IT 24.011 and EUCENTRE ICE039E23_TR_1. Each report relates to the tested conditions and configuration; ICEL checks its relevance to the requested supply.

Explore the details
Has LPC undergone internal arcing testing?

Yes. The catalogue lists ACAE–LOVAG test IT 24.011 to IEC TR 61641 Ed. 3 at 100 kA for 0.3 s, criteria 1 to 5, and a dielectric test. These results refer to the tested configuration and are distinct from the rated short-time withstand current Icw.

Explore the details
Is seismic qualification documented?

The catalogue lists EUCENTRE (ACCREDIA) report ICE039E23_TR_1: severity level II, with accelerations of 1.0 g horizontally and 0.8 g vertically. Applicability to a project must be checked against the configuration and installation conditions.

Explore the details
What dimensions and installation conditions apply?

The technical data sheet lists a height of 2,250 mm, base depths of 1,000, 1,200 or 1,400 mm and section widths of 500, 600, 700, 850, 1,000 or 1,100 mm. Installation is stationary and indoors, on a level floor. Overall dimensions, access clearances and section configuration are defined in the project drawings.

Explore the details
What is needed to request an LPC Power Center quotation?

The technical discussion starts with the single-line diagram, network characteristics, required currents, loads and their diversity. It also considers the form of separation, circuit-breakers, cable or busbar connections, auxiliary circuits, service environment and available space.

Send a quotation request

LPC / DIGITAL CATALOGUESource: ICEL technical catalogue, IT+EN V2.0, 04.03.2024.

Data and illustrations are not binding. ICEL reserves the right to make changes during product development. Supply characteristics are defined for each project.

Back to top ↑

YOUR NEXT PROJECT STARTS HERE

LET’S GIVE
YOUR IDEAS
POWER.

A project to develop, a partnership to propose or a question to ask. Let’s start here.

01 / Tell us what you need

02 / Share the relevant documents

03 / Let’s define the solution